-Inputs: Dedicated Single Zone -Output Signal: 1 SPDT, 5 Amp, 240 VAC rated alarm relays and 1, SPDT, 5 Amp, -240 VAC rated system fault relay, plus a Digital Display w/ a dedicated 4–20mA DC analog output -Detector Type: Single Pass, Non-dispersive Infrared -Measuring Range: 0 to 20,000ppm -Sensitivity: 1ppm -Accuracy: ±15ppm (readings ≤ 100ppm); ±10% (100ppm>readings≤20,000ppm) -Data Logger: 200 data points stored in non-volatile memory -Communications(optional): RS485, Modbus -Response Time: 200 mS plus sample lag -Sample Flow Rate: < 1L/min -Calibration Interval: Automatic/Every 6 minutes -Back Purge: Fully Automatic(sample line and probe) -Sample Conditioning: Integral for moisture and particulate -Power: 120/230 VAC, 50/60 Hz -Dimensions: 28" x 22" x 9" NEMA 12 wall or rack mountable |

products 


Electronics Specification